Loads

Loads on falsework

The vertical loads applied on falsework are defined as per below

DLThe minimum self-weight of the formwork: \(DL = 0.48 kPa\) or \(10 psf\)
LLWeight of workers, tool and equipment: \(LL = 1.9 kPa\) or \(40 psf\)
When concrete placing is done with motorized equipment or for heavy civil construction (bridge, subways and tunnels): \(LL = 3.1 kPa\) or \(65 psf\).
CConcrete density: \(\rho_c = 24 \frac{kN}{m^3}\) or \(150 \frac{lb}{ft^3}\)
Concrete weight: \(C = \rho_ch\) where h is the concrete depth
Minimum concrete weight: \(C = 2.4 kPa\) or \(50 psf\) (equivalent to a 100mm depth of concrete)
Clause 5.4.2

The horizontal loads applied on falsework are defined as per below

WThe wind load can’t be less than recommended by the National Building Code of Canada (NBC) with 1/50 probability, gust factor of 2 and reduction factor of 0.75 for falsework erected during less than 2 years.
HThe greater force between 2% of the total vertical loads or \(H = 1.46 \frac{kN}{m}\) or \(100 \frac{lb}{ft}\) applied at the slab edge
EBecause of the temporary nature of the structures; seismic, rain and snow loads are in general neglected
Clause 5.4.3
Loads on formwork

The horizontal loads applied on formwork are defined as per below

WThe wind load can’t be less than recommended by the National Building Code of Canada (NBC) with 1/50 probability, gust factor of 2 and reduction factor of 0.75 but not less than \(W = 0.8 kPa\) or \(16.5 psf\)
Clause 5.5.2
PWall form up to 1.2m high must be design for full liquid head pressure. From this clause we can assume any wall, higher than 1.2m should be design for minimum \(P=\rho_c\times h=28.8kPa\) or \(600 psf\) where \(h=1.2m\).
Clause 5.5.3.3.1.3.2
PFor formwork 3m above ground or within 3m for an open edge must be design for minimum \(P = 48 kPa\) or \(1000 psf\).
Clause 5.5.3.3.1.3.3